Skip to product information
Y503-222-L LoRaWAN RTU, 2DI/2DO/2AI and RS485

Y503-2220-L LoRaWAN RTU, 2DI/2DO/2AI and RS485

Y503-2220-L connects two digital inputs, two switched voltage outputs, a 0–10 V input, a 4–20 mA input and isolated RS485 to a LoRaWAN gateway and Network Server.

Protocol
LoRaWAN 1.0.3
Channels
2 DI with shared COM
Voltage Input
1 fixed AV terminal, 0–10 V
Current Input
1 fixed AI terminal, 4–20 mA
$72.00

Price for the selected configuration.

Frequency Band

Shipping & Tax: Shipping is quoted separately and paid before dispatch. Import duties, taxes, customs fees and destination charges are paid by the customer.

View Shipping Policy

1-Year Warranty

Expert Technical Support

Overview

Y503-2220-L connects two digital inputs, two switched voltage outputs, a 0–10 V input, a 4–20 mA input and isolated RS485 to a LoRaWAN gateway and Network Server.

Key Features

  • Two digital inputs share COM and accept dry contacts or powered signals up to 28 VDC, with wiring matched to the sensor
  • Two switched voltage outputs follow the RTU supply voltage; they are not dry relay contacts
  • Separate fixed-function analog terminals: one 0–10 V AV input and one 4–20 mA AI input, with no analog output
  • Isolated RS485 supports configured polling and transparent transport, including Modbus RTU data
  • LoRaWAN 1.0.3, OTAA/ABP and Class A/Class C, with periodic, heartbeat and state-change reporting
  • Timed output, pulse control and local input-to-output rules require compatible firmware and a confirmed output-load rating

How it works & selection

Selection notes

Confirm regional plan, DI wiring, DO voltage and combined load, sensor signals, firmware and payload definitions before ordering. The two outputs are switched voltage outputs, not dry relay contacts.

Ask YenGear to check your configuration

Technical specifications

ProtocolLoRaWAN 1.0.3
Channels2 DI with shared COM
Voltage Input1 fixed AV terminal, 0–10 V
Current Input1 fixed AI terminal, 4–20 mA
LoRaWAN Radio
Protocol LoRaWAN 1.0.3
Activation OTAA / ABP
Device Classes Class A / Class C
Frequency Plans EU433, CN470 (reference), EU868, AU915, US915, AS923; region-specific hardware; specify the AS923 sub-plan when ordering
Transmit Power -1 to 22 dBm, subject to regional configuration
Bandwidth 125 kHz
Spreading Factor SF7–SF12
Receiver Sensitivity -135 dBm at SF12, BW125 kHz
Digital Inputs
Channels 2 DI with shared COM
Signal Types Dry contact or powered contact; NPN/PNP wiring depends on COM connection
Maximum Voltage DC 28 V
Digital Outputs
Channels 2 switched voltage outputs
On State Voltage Follows the applied RTU supply voltage
Output Type Voltage outputs, not voltage-free relay contacts or analog outputs
Current Limit Maximum specified output current: 1 A. Contact YenGear for per-channel and combined load limits before connecting two loads.
Supply Sizing Use a 2 A adapter when the connected output load exceeds 200 mA; budget combined loads and starting current
Analog Inputs
Voltage Input 1 fixed AV terminal, 0–10 V
Current Input 1 fixed AI terminal, 4–20 mA
Accuracy ±0.5% of full scale
Reported Resolution 0.001 V / 0.001 mA; measurement accuracy is ±0.5% of full scale
Analog Outputs None
Maximum Input 10.7 V at AV; 22 mA at AI. Normal measurement ranges are 0–10 V and 4–20 mA.
Serial Interface
RS485 1 isolated RS485 A/B
Esd Protection 15 kV
Baud Rates 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 bps
Format 8 data bits; 1 or 2 stop bits; none, odd, or even parity
Initial Setting 9600 bps, 8-N-1
Operation Scheduled polling and transparent transport, including configured Modbus RTU frames
Reporting And Control
Reporting Periodic acquisition, heartbeat, and input/output state-change reporting
Control Remote output commands; timed control, pulse output, and local input-to-output rules require compatible firmware
Commissioning Check startup state and communication-loss behavior for the installed firmware. A radio acknowledgement does not prove that the connected equipment changed state.
Power Supply
Voltage DC 9–28 V; use one supply for parallel power inputs
Reference Adapter DC 12 V / 1 A; larger supply where required by output load
Maximum Working Current 0.5 A for the RTU; budget controlled loads separately
Average Power ≤0.5 W; load and operating conditions affect total consumption
Environmental
Operating Temperature -40 to 85 °C
Storage Temperature -50 to 95 °C
Humidity 5–95% RH, non-condensing
Mechanical
Dimensions 104 × 97.6 × 25.6 mm
Weight Approximately 0.7 kg
Mounting Wall or panel surface; follow supplied mounting drawing
Antenna Connector SMA female
Deployment
Gateway Compatibility Y501-L or Y511-L with matching regional plan and channels, using an external Network Server or optional local NS/AS
Downlinks Class A receives downlinks after an uplink. Class C provides more receive opportunities. Delivery time depends on airtime, server scheduling and regional radio limits.
Payload Configuration tools, uplink decoders and downlink commands must match the installed firmware

Package & resources