Y402-11-L 1DI + 1DO LoRa One-to-Many I/O System
Y402-11-L is a one-to-many LoRa I/O system with one master and one or more slave units.
- Product type / topology
- One-to-many, bidirectional
- Channels
- 1DI + 1DO per master/slave
- Input signals
- 1 × passive dry-contact / NPN open-collector input per master/slave; no voltage input to DI
- Power supply
- 9–36 VDC
$89.00
Price for the selected configuration.
Shipping & Tax: Estimate shipping in your cart. Available options and final charges are confirmed at checkout.
Import duties, taxes, customs fees and destination charges are paid by the customer. View Shipping Policy
Overview
Y402-11-L is a one-to-many LoRa I/O system with one master and one or more slave units. It is used when one central point needs to exchange a single dry-contact signal with multiple remote locations.
Typical applications
- One master controlling multiple remote relay outputs.
- Remote alarm feedback from several field points to one control point.
- Distributed pump, valve, gate, and lighting control without long signal cabling.
How it works & selection
- Master DI closed: DO on all slave units energizes.
- Any slave DI closed: master DO energizes.
- The master output resets only after every slave DI returns to open.
Selection notes
Confirm how many slave units are needed. The kit configuration changes with node count.
Technical specifications
| Product type / topology | One-to-many, bidirectional |
|---|---|
| Channels | 1DI + 1DO per master/slave |
| Input signals | 1 × passive dry-contact / NPN open-collector input per master/slave; no voltage input to DI |
| Power supply | 9–36 VDC |
Signals and communication
| Product type / topology | One-to-many, bidirectional |
|---|---|
| Channels | 1DI + 1DO per master/slave |
| Signal mapping | Master DI to all slave DO; slave DI to master DO; bidirectional |
| System configuration | 1 master + 1–6 slaves (current product options) |
| Frequency band | 398–525 MHz |
| Communication range | Up to 5 km (open area; model, antenna, and site dependent) |
Electrical
| Power supply | 9–36 VDC |
|---|---|
| Power consumption | Master: 1 W max.; slave: 0.8 W max. |
| Input signals | 1 × passive dry-contact / NPN open-collector input per master/slave; no voltage input to DI |
| Relay outputs | 1 × SPDT relay per master/slave; AC 277 V / 5 A or DC 28 V / 5 A |
Mechanical and environment
| Dimensions | Master: 88 × 72 × 59 mm; slave: 88 × 37 × 59 mm |
|---|---|
| Mounting | 35 mm DIN rail |
| Environment | −20 to +85 °C; 10% to 90% RH, non-condensing |
| Protection | IP20 |
Package & resources
Package contents
| Item | Qty. |
|---|---|
| Y402-11-L master module | 1 |
| Y402-11-L slave module | 1 |
| 470 MHz magnetic-mount antennas | 2 |
| DIN rail clips | 2 |
| Quick reference guide | 1 |
| Warranty card | 1 |