Skip to product information
Y402-11-L 1DI + 1DO LoRa One-to-Many I/O System
Y402-11-L is a one-to-many LoRa I/O system with one master and one or more slave units.
- Product type / topology
- One-to-many, bidirectional
- Channels
- 1DI + 1DO per master/slave
- Input signals
- 1 × passive dry-contact / NPN open-collector input per master/slave; no voltage input to DI
- Power supply
- 9–36 VDC
$89.00
Price for the selected configuration.
Shipping & tax
Shipping options and rates are confirmed at checkout.
Import duties, taxes and destination fees are paid by the customer. Shipping policy
Overview
Y402-11-L is a one-to-many LoRa I/O system with one master and one or more slave units. It is used when one central point needs to exchange a single dry-contact signal with multiple remote locations.
Typical applications
- One master controlling multiple remote relay outputs.
- Remote alarm feedback from several field points to one control point.
- Distributed pump, valve, gate, and lighting control without long signal cabling.
How it works & selection
- Master DI closed: DO on all slave units energizes.
- Any slave DI closed: master DO energizes.
- The master output resets only after every slave DI returns to open.
Selection notes
Confirm how many slave units are needed. The kit configuration changes with node count.
Technical specifications
| Product type / topology | One-to-many, bidirectional |
|---|---|
| Channels | 1DI + 1DO per master/slave |
| Input signals | 1 × passive dry-contact / NPN open-collector input per master/slave; no voltage input to DI |
| Power supply | 9–36 VDC |
Signals and communication
| Product type / topology | One-to-many, bidirectional |
|---|---|
| Channels | 1DI + 1DO per master/slave |
| Signal mapping | Master DI to all slave DO; slave DI to master DO; bidirectional |
| System configuration | 1 master + 1–6 slaves (current product options) |
| Frequency band | 398–525 MHz |
| Communication range | Up to 5 km (open area; model, antenna, and site dependent) |
Electrical
| Power supply | 9–36 VDC |
|---|---|
| Power consumption | Master: 1 W max.; slave: 0.8 W max. |
| Input signals | 1 × passive dry-contact / NPN open-collector input per master/slave; no voltage input to DI |
| Relay outputs | 1 × SPDT relay per master/slave; AC 277 V / 5 A or DC 28 V / 5 A |
Mechanical and environment
| Dimensions | Master: 88 × 72 × 59 mm; slave: 88 × 37 × 59 mm |
|---|---|
| Mounting | 35 mm DIN rail |
| Environment | −20 to +85 °C; 10% to 90% RH, non-condensing |
| Protection | IP20 |
Package & resources
Documents & support
Specification
Package contents
| Item | Qty. |
|---|---|
| Y402-11-L master module | 1 |
| Y402-11-L slave module | 1 |
| 470 MHz magnetic-mount antennas | 2 |
| DIN rail clips | 2 |
| Quick reference guide | 1 |
| Warranty card | 1 |